  • UHV-S10A Three-circuit Transformer DC Resistance Tester

    The instrument has big current output and can select current automatically; convenient for operation.Possessing perfect protective circuit which is highly reliable.Industrial plastic shell case with light weight; convenient for carrying.

    Product Details of UHV-S10A Three-circuit Transformer DC Resistance Tester


    Product Introduction

    This DC resistance rapid tester is the latest generation product for measuring the DC resistance of transformers, optimized for measuring the DC resistance of three-phase windings in large capacity transformers. Simultaneously test the DC resistance of the three-phase winding of the transformer.


    技術的パラメータ

    Testing currentSingle phase:1A 5A 10A 20A
    Three phase:1A 5A 10A
    Measurement scopeSingle phase
    1A 10mΩ ~ 20Ω
    5A 1mΩ ~ 4Ω
    10A 1mΩ ~ 2Ω
    20A 1mΩ ~ 1Ω
    Three phase
    1A 10mΩ ~ 6Ω (each phase)
    5A 1mΩ ~ 1Ω (each phase)
    10A 1mΩ ~ 0.6Ω (each phase)
    測定精度± (0.2%Full span ± 2 words )
    Maximum resolution0.1mΩ
    Data storage capacity150 groups
    電源AC 220V±22V,50Hz±2Hz
    作業環境Ambient temperature: 0°~40° Relative humidity :≤80%


    Product Features:

    1. Simultaneously test the DC resistance of the three-phase winding of the transformer.

    2. For on load tap changers, there is no need for discharge, and the tap changer can be directly adjusted. The measurement time is one-third of traditional single-phase measurement, which can greatly shorten the working time and labor intensity.

    3. The direct resistance meter adopts a large screen LCD display with a fully Chinese graphical interface, which is clear and intuitive, and the operation is very simple.

    4. And equipped with a panel printer and large capacity non-volatile memory, it can conveniently store and print measurement results.

    5. The test data is stable, fast, and has good repeatability, making it the best choice for on-site measurement of transformer DC resistance.


    Matters needing attention:

    1. When measuring an unloaded voltage regulating transformer, the discharge must be exited before switching the tap changer. The tap changer can only be switched after the discharge indication is complete

    2. It is not allowed to dismantle the wiring during the measurement process.

    3. If the charging progress bar and current display value remain stagnant for a long time, the measured winding resistance may exceed the current measurement range, and the current may not reach the preset value. At this point, you can press the 'Exit' button to return, select the current again, and try again.

    4. When replacing the fuse and accessories, please use the same model as this instrument