qiao@hvtest.cc15871365102
  • UHV-1200 6相リレーテスタ 二次注入試験

    UHV-1200 6 相リレーテスター二次注入テストは、最大 6 相電圧および 6 相電流までの電圧と電流出力の柔軟な組み合わせで、従来の 4 相電圧、3 相電流タイプ、6 相電圧タイプ、6 相電圧タイプを実現するために任意の組み合わせが可能です。相電流タイプ、12相出力モードを搭載しており、従来の各種試験法に対応するだけでなく、三相変圧器の差動試験やプラント電源の速断・即時自己注入試験にも便利です。

    UHV-1200 6相リレーテスタ2次注入試験の製品詳細


    Product Introduction

    The UHV-1200 Microcomputer Relay Protection Tester features a highly flexible combination of voltage and current outputs, supporting up to 6-phase voltage and 6-phase current channels. It allows users to configure various

    output modes, such as the conventional 4-phase voltage and 3-phase current setup, 6-phase voltage output, or combined 6-phase and 12-phase output modes. This design ensures compatibility with traditional testing

    methods and also facilitates advanced applications such as differential testing of three-phase transformers, fast bus transfer tests, and backup auto-reclosing verification.

    The high-performance main unit employs DSP control in its output section, providing fast processing speeds, strong real-time digital signal processing capabilities, wide transmission bandwidth, and high-resolution D/A

    conversion. This ensures high waveform precision, minimal distortion, and excellent linearity in output signals.

    Through the application of advanced technologies, precision components, and materials—along with a professional structural design—the device achieves a compact and lightweight form factor without compromising

    functionality. It is fully portable, easy to set up, and convenient for on-site or mobile testing applications.


    製品の特徴

    1、Flexible Output Configuration

    Supports up to 6-phase voltage and 6-phase current outputs, configurable in various modes for compatibility with conventional testing, differential protection, and advanced grid simulations.

    2、High-Fidelity Power Amplifier

    Utilizes modular linear power amplifiers to ensure clean, stable waveforms without medium/high-frequency interference.

    3、High-Performance DSP Control

    DSP-based output with fast processing, high-resolution D/A conversion, and excellent waveform accuracy.

    4、Compact and Portable Design

    Lightweight, integrated structure with full functionality for easy transport and field testing.

    5、Comprehensive Software Suite

    Enables automated testing, fault simulation, data storage, vector display, and report generation.

    6、Independent DC Power Output

    Includes 110V/220V adjustable DC power supply for auxiliary testing.

    7、Extensive Connectivity

    Features USB and other communication interfaces for PC connection and external device integration.

    8、Built-in Protection Mechanisms

    Incorporates thermal management, soft-start, fault diagnostics, and output lockout for safe operation.

    9、Laptop-Compatible Operation

    Can be operated with an external laptop using the same intuitive software interface.


    6 Phase Relay Tester 1
    6 Phase Relay Tester 2


    製品パラメータ

    Argument

    現在のチャンネル番号Standard 6 phase
    電圧チャンネル番号Standard 6 phase
    Ac current output range30A/phase or 180A (six parallel)
    Dc current output range10A DC/phase
    Ac voltage output range120V AC/phase
    Dc voltage output range160V DC/phase

    AC電流出力

    6 phase current output per phase(effective value)0~30A output precision 0.2
    3 phase current output per phase(effective value)0~60A
    6 phase parallel current output(RMS)0~180A
    Phase current long-term allowable working value(RMS)10A
    Maximum output power of phase current450VA
    T6 phase parallel current maximum output power1000VA
    6 Allowable working time for maximum output of phase parallel current10代
    Frequency range(fundamental)0~1000Hz
    Harmonic frequency0 to 20 times

    直流電流出力

    電流出力0~±10A/phase output accuracy 0.5 level
    Maximum output load voltage20V

    交流電圧出力

    Phase voltage output(RMS)0~120V output precision 0.2
    Line voltage output(RMS)0~240V
    Phase voltage/line voltage output work80VA/100VA
    周波数範囲(基本波)0~1000Hz
    Harmonic frequency0 to 20 times

    直流電圧出力

    Phase voltage output amplitude0~±160V output accuracy 0.5
    Line voltage output amplitude0~±320V
    Phase voltage/line voltage output power70VA/140VA

    Switching value

    8 switch inputsNull contact 1~20mA, 24V
    0 Potential contact access "0" : 0~+6V; 1: +11V to +250V
    4 pairs of switching outputDC:220V/0.2A; AC:220V/0.5A

    時間測定範囲

    時間測定範囲0.1ms~9999s
    測定精度0<0.1mS

    6 Phase Relay Tester 3
    6 Phase Relay Tester 4


    Core functionality

    1. Multi channel analog output: capable of outputting AC, DC current, voltage, and phase signals, simulating various power system operating states and typical fault situations, such as overcurrent, undervoltage, differential, and distance protection.

    2. Action time measurement: Accurately record the time from receiving the signal to completing the action of the relay protection device, ensuring that it meets the standard requirements, thereby ensuring rapid fault removal.

    3. Action value verification: It can test whether the action current and voltage values set by the protection device are consistent with the actual action values, and verify the accuracy and sensitivity of the device.

    4. Logic function testing: supports simulation and verification of complex protection logic, such as multi-stage overcurrent protection, linkage tripping, and automatic reclosing logic, to ensure that the protection strategy is effective in actual operation.

    5. Data recording and analysis: Modern testers usually have data storage and intelligent analysis functions, which can generate test reports for historical data comparison, trend analysis, and operation and maintenance management.


    Application scenarios:

    1. Acceptance of newly put into operation device: After the installation of the protective device, comprehensively test its action values, time limits, and logical functions to ensure compliance with the requirements of the fixed value sheet.

    2. Regular inspection: Regularly verify the protection (such as differential, distance, overcurrent protection) during operation according to regulations to ensure its reliability.

    3. Post fault analysis: After a system malfunction, simulate the fault quantity to test the protective action behavior and determine whether there is refusal, misoperation, or characteristic drift.

    4. Protection system transmission test: Apply simulated fault current and voltage to verify the correctness of the entire circuit from relay sensing fault to circuit breaker tripping.


    Product Frequently Asked Questions

    1. What protection devices can the relay protection tester test? It covers almost all common types of protection, including line protection, transformer protection, busbar protection, generator protection, motor protection, differential protection, distance protection, overcurrent protection, and low cycle load shedding devices.

    2. Why doesn't the protective device work? In most cases, it is related to wiring errors, incorrect setting of settings, improper selection of test items, or abnormal wiring of input and output circuits.

    3. How to deal with the inability to output test voltage? Firstly, confirm the software parameter settings. Secondly, check the fuse, output switch, and voltage circuit wiring.

    4. Does the relay protection tester need to be grounded? The answer is that it must be grounded. Good grounding is not only related to the accuracy of test results, but also to the safety of test personnel.

    5. Why does the repetition of action time decrease? Common causes include fluctuations in auxiliary power supply, poor contact of contacts, internal faults in protective devices, and environmental electromagnetic interference.

    6. What are the most common problems during distance protection testing? Impedance calculation errors and polarity reversal are the two most common problems on site.

    7. How to choose between six phase equipment and three-phase equipment? For units with more tests on line protection, transformer protection, and differential protection, six phase equipment can significantly improve work efficiency.

    8. How to choose a reliable manufacturer of relay protection tester? Attention should be paid to product accuracy, software functionality, after-sales service, and manufacturer's technical strength. For example, Wuhan UHV Power Technology Co., Ltd.










    あなたはおそらくそれも好きでしょう

    • 何か質問がある!

      いつでもお気軽にご連絡ください
      お問い合わせ
    • ご来店ください

      6号館、光学谷光学機械産業園区、高新5路84号、
      中国湖北省武漢市東湖新技術開発区

    • 私達に電子メールを送り

      qiao@hvtest.cc

    • お電話ください

      +86-15871365102